Appendix C – Setup for Carbon / Dual Temperature for Quench Control
SSi’s 9205 controller is capable of controlling %Carbon and Dual Temperature loops for the purpose of quench tank control. This guide describes how to use SSi’s Configurator to set up the 9205 controller for %Carbon and Dual Temperature control.
Procedure
-
Make sure that two (2) relay outputs are available. Configure the relay outputs for Alarm 1 and Alarm 2 under Relay Assignments. See Relay Assignments.
Configuring two relay outputs for Alarm 1 and Alarm 2 relay assignments
-
Configure Alarms 1 & 2 for deviation alarms to activate the relays when heating or cooling is needed. AL1 would be for cooling, AL2 for heating.
|
Configuring Alarm 1 and Alarm 2 as deviation alarms with appropriate settings
-
Check the menu Passcode and Alarm to ensure that alarms 1 & 2 are set up for a “normally open” condition.
Setting up Alarm 1 and Alarm 2 as "normally open "