What do the alarm codes mean on my eFlo?
Alarm Code | Possible Causes | Possible Corrective Actions |
LoPr - Low Pressure |
Activated when low pressure has been indicated based on either factory or user specified values
*factory values are not editable and cannot be deactivated; call SSI with any questions |
Increase regulator pressure Verify all upstream solenoids and/or ball valves are open
*make sure not to exceed pressure limits for the sensors indicated on page 6 |
hiPr - High Pressure |
Activated when high pressure has been indicated based on either factory or user specified values
If indicated pressure is above the range of the sensor, the meter WILL NOT show accurate values
*factory values are not editable and cannot be deactivated; call SSI with any questions |
Decrease regulator pressure below the usable range of the sensors
*make sure not to exceed pressure limits for the sensors indicated on page 6 |
LofL - Low Flow | Activated when low flow has been indicated based on user specified values |
Increase flow rate on meter to a value above what has been set
It is possible that low pressure is limiting the flow rate and pressure should be increased
It is also possible that high pressure has been achieved and the meter is now reading incorrectly |
hifL - High Flow | Activated when high flow has been indicated based on user specified values |
Increase flow rate on meter to a value above what has been set
It is possible that low pressure is limiting the flow rate and pressure should be increased |