Appendix C: Register Map
Register(s) |
Description |
---|---|
file 0 |
|
0 |
firmware version x 100 |
1 |
RS232 host port Baud (terms 1,2,& 3) |
2 |
RS232 host port; Modbus slave = 1 |
3 |
RS485 Slave port Baud (0 to 13 for 1200 to 921600) |
4 |
RS485 Slave port; 0 = MMI master, 1 = Modbus master |
5 |
Not used reserved |
6 |
Not used reserved |
7 |
RS485 port Baud (0 to 13 for 1200 to 921600) |
8 |
RS485 port; Modbus master = 1, host port = 9 |
9 |
PIC COMS baud |
10 |
PIC coms mode (not used) |
11 |
RS232 port baud (terms 4,5,& 6) |
12 |
RS232 port mode: Modbus slave = 1, Modbus master = 9 |
13 |
forced to 1 for MGA |
14 |
|
15 |
0 = degree F; 1 = degree C |
16 |
zone number |
17 |
zone sequence |
18 |
max number of zones (8 or less) |
19 |
|
20 |
Dwell Timer |
21-25 |
|
26 |
Instrument calculation enable and time per step. (ms) 10 MS min |
27 |
start smart board detect routine |
28 -32 |
|
33 |
Baud set flag port F |
34 |
if 1 enable pressure compensation |
35 |
pressure trim value |
36-42 |
|
43 |
Startup pressure reading kPa * 100 |
44 |
elevation change from startup in feet * 10 |
45 |
Elevation from sea level in feet |
46 |
pressure trim value |
47 |
Local pressure entered for calibration |
48 |
o2 calibration factor (10000 nom) |
49 |
o2 zero offset |
50 |
pressure reading in kPa * 100 |
51 |
pressure difference due to elevation in kPa * 100 |
52 |
sea level (barometric) pressure |
53 |
pressure in atmospheres * 1000 |
54 |
pressure in inHG * 100 |
55 |
upstream pressure reading in kPa * 100 |
56 |
upstream sea level (barometric) pressure |
57 |
upstream pressure in atmospheres * 1000 |
58 |
upstream pressure in inHG * 100 |
59 |
pressure sensor and calculation select; |
60 |
pressure diff upstream to downstream in kPa * 100 |
61 |
sample flow |
62-63 |
|
64 |
flow zero offset |
65 |
flow span value |
66 |
|
67 |
Dualpro process factor register |
68 |
LED D2 ON time in milliseconds |
69 |
LED D2 OFF time in milliseconds |
70 |
|
71 |
must be 123 to accept cal request for cell |
72-73 |
|
74 |
Web change enable; 0 = disable, 1 = enable |
75 |
|
76 |
Sample/Pump ON delay same value all zones |
77 |
Sample/Pump OFF delay same value all zones |
78-79 |
|
80 |
H2 zero gas % times 100 (xx.xx) |
81 |
H2 span gas % times 100 (xx.xx) |
82 |
hydrogen cell calibration request; 1 = zero, 2 = span |
83 |
Low Dew point cell source;0 = not used, 1 thru 40 = Smart AIB input number |
|
|
84 |
Present reading from low dew point cell; xxx.x in deg C or def F |
85 - 92 |
Zone low dew point data (reg 85 - 92) |
93 |
|
94 |
O2 data source: 0 = O2_blk, 1 thru 40 = Smart AIB input number |
|
|
95 |
Est temperature of the lambda probe based on degree |
96 |
pump run time |
97 |
|
98 |
|
99 |
|
100 |
local cooler ON set point |
101 |
local cooler OFF set point |
102 |
local temperature x 10 in deg F or C based on degree |
103 |
Auto cal interval in minutes 0 = OFF |
104 |
Auto Zero interval in minutes 0 = OFF |
105 |
Auto data display time at end of seq |
106 |
purge time before cal or zero |
107 |
if auto cal is avail this is 1 |
108 |
Zone alarm relays output desired states |
109 |
relays output desired states:0 = pump, 1 = Alarm 2, 2 = Alarm 1, 3 = Aux cal gas, 4 = Sample, 5 = ACZ gas, 6 = ACZ span gas, 7 = AC/cooler on |
110 |
bits 0 - 3 = sample relays zones 1 - 4; bits 4 - 7 = Zone ON zones 1 - 4 |
111 |
bits 0 - 3 = sample relays zones 5 - 8; bits 4 - 7 = Zone ON zones 5 - 8 |
112 |
|
113 |
O2 data mantissa |
114 |
O2 data exponent |
115 |
HI range CO2 data xx.xx% |
116 |
CO data xx.xx% |
117 |
CO2 data x.xxxx% max 3.0000% |
118 |
O2 data xx.x% |
119 |
CH4 data xx.xx% |
120 |
Ratio CO2/CO |
128 |
IR Dew point if calculated |
136 |
IR %C |
144 |
IR suggested COF |
152 |
IR suggested PF |
160 |
IR equivalent millivolts |
168 |
sample flow at calc time |
176 |
Calculated new factor for COF/PF adjust |
184 |
HI range CO2 data xx.xx% |
192 |
CO data xx.xx% |
200 |
CO2 data x.xxxx% max 3.0000% |
208 |
O2 data xx.x% |
216 |
CH4 data xx.xx% |
224 |
sample temperature |
232 |
sample pressure upstream |
240 |
sample pressure downstream |
248-249 |
|
|
|
File 3 |
|
600-609 |
|
610 |
IR cell seq flag |
611 |
IR calibration requests |
612 |
calibration mode |
613 |
calibration timer for purge, etc |
614 |
calibration counter |
615 |
calibration enable CO |
616 |
calibration enable CO2 |
617 |
calibration enable CH4 |
618 |
calibration enable CO2H |
619 |
|
620 |
calibration alarm bit map |
621-639 |
|
640 |
calibration span gas 1 |
641 |
calibration span gas 2 |
642 |
calibration span gas 3 x.xxxx |
643 |
calibration span gas 4 |
644 |
calibration span gas 5 |
645 |
auto calibration span gas 2 |
646 |
auto calibration span gas 3 x.xxxx |
647 |
auto calibration span gas 4 |
648 |
auto calibration span gas 5 |
649 |
aux calibration span gas 2 |
650 |
aux calibration span gas 3 x.xxxx |
651 |
aux calibration span gas 4 |
652 |
aux calibration span gas 5 |
653 |
sample calibration span gas 2 |
654 |
sample calibration span gas 3 x.xxxx |
655 |
sample calibration span gas 4 |
656 |
sample calibration span gas 5 |
657 |
calibration gas source; Forced to 0 for RZA |
658-665 |
|
666 |
|
667 |
|
668 |
ambient temperature trim; deg C * 100 |
669 |
gas (cell) temperature trim; deg C * 100 |
670 |
AIB board 1 input 1 type |
671 |
AIB board 1 input 2 type |
672 |
AIB board 1 input 3 type |
673 |
AIB board 2 input 1 type |
674 |
AIB board 2 input 2 type |
675 |
AIB board 2 input 3 type |
676 |
AIB board 3 input 1 type |
677 |
AIB board 3 input 2 type |
678 |
AIB board 3 input 3 type |
679 |
AIB board 4 input 1 type |
680 |
AIB board 4 input 2 type |
681 |
AIB board 4 input 3 type |
682 |
AIB board 5 input 1 type |
683 |
AIB board 5 input 2 type |
684 |
AIB board 5 input 3 type |
685 |
AIB board 6 input 1 type |
686 |
AIB board 6 input 2 type |
687 |
AIB board 6 input 3 type |
688 |
AIB board 7 input 1 type |
689 |
AIB board 7 input 2 type |
690 |
AIB board 7 input 3 type |
691 |
AIB board 8 input 1 type |
692 |
AIB board 8 input 2 type |
693 |
AIB board 8 input 3 type |
694 |
Board number to calibrate 1 to 8 |
695 |
enables a calibration |
696 |
CJ cal or zero/span voltage cal |
697 |
Calibration Range register. Sets the voltage gain for a calibration. |
698 |
bitmap of channels to be calibrated |
699 |
Calibration value for all inputs |
|
|
file 2 |
|
700 |
alloy factor for calculation 10000 = 1.0000 |
708 |
default Hydrogen to use if no H2 cell 40% = 40.00 |
716 |
0 = original sin, 1 = CarbCalc_Caf1, 2 = CarbCalc Caf, 3 = COCO2 Caf1, 4 = COCO2 Caf |
724 |
IR shim factor |
732 |
Pressure compensation factor; 0 = off, 10 = 1.0, max 2.0 |
740 |
CH4 factor |
748 |
IR CO compensation factor |
756 |
pump mode; 0 = off, 1 & 2 = auto |
764 |
mode: 0 = monitor, 1 = COF/PF adjust base on %C |
772 |
max adjust amount |
780 |
maximum COF/PF |
788 |
minimum COF/PF |
796 |
Probe ATM instrument; -1 = internal (Input 1 for MV Input 2 for TC), |
|
-2 = internal (Input 1 for MV Input 3 for TC), 0 to Probe ATM max for external, |
|
use -3 for manual |
|
-4 for data in external table |
|
Probe ATM inst number is type for inst setup [0][0]; |
804 |
Probe temperature instrument; -1 = internal (Input 3 for furn TC), |
|
-2 = internal (Input 2 for furn TC), 0 to Probe TC max for external, |
|
use -3 for manual |
|
-4 for data in external table |
|
Probe TC inst number + 256 is type for inst setup[1][0] |
812 |
Dwell Times in seconds min 30 max 300 |
820 |
zone active; 0 = no, 1 = yes |
828 |
Adjust/control update interval |
836 |
Select CO2 for calculation: 0 = normal IR gas[2] , 1 = high range IR gas[4] |
844 |
Enable IR Dew point calculation |
852 |
IR dew point factor |
860 |
Adjust minimum temperature |
868 |
Adjust minimum millivolts |
876 |
Minimum MV action; 0 = only inhibits adjust and control |
884 |
sample control; 0 = off, 1 = on |
892 |
|
893 |
Ambient temperature Low alarm limit |
894 |
Ambient temperature High alarm limit |
895 |
Ambient temperature Low alarm limit |
896 |
Ambient temperature High alarm limit |
897 |
O2 cal span value 209 = 20.9% |
898 |
O2 calibration req; 1 = zero, 2 = span |
899 |
return code of UDPDL init() |
|
|
file 4 [2][] |
|
|
Dac assignx => gas number * 8 + zone number |
|
bit 12 sets output; 0 = 4 - 20MA, 1 = 0 - 20MA |
9000 |
Brd 1 Dac 1 assignment |
9001 |
Brd 1 Dac 2 assignment |
9002 |
Brd 1 Dac 3 assignment |
9003 |
Brd 1 Dac 4 assignment |
9004 |
Brd 1 Dac 1 zero |
9005 |
Brd 1 Dac 1 span |
9006 |
Brd 1 Dac 2 zero |
9007 |
Brd 1 Dac 2 span |
9008 |
Brd 1 Dac 3 zero |
9009 |
Brd 1 Dac 3 span |
9010 |
Brd 1 Dac 4 zero |
9011 |
Brd 1 Dac 4 span |
9012 |
Brd 2 Dac 1 assignment |
9013 |
Brd 2 Dac 2 assignment |
9014 |
Brd 2 Dac 3 assignment |
9015 |
Brd 2 Dac 4 assignment |
9016 |
Brd 2 Dac 1 zero |
9017 |
Brd 2 Dac 1 span |
9018 |
Brd 2 Dac 2 zero |
9019 |
Brd 2 Dac 2 span |
9020 |
Brd 2 Dac 3 zero |
9021 |
Brd 2 Dac 3 span |
9022 |
Brd 2 Dac 4 zero |
9023 |
Brd 2 Dac 4 span |
9024 |
Brd 3 Dac 1 assignment |
9025 |
Brd 3 Dac 2 assignment |
9026 |
Brd 3 Dac 3 assignment |
9027 |
Brd 3 Dac 4 assignment |
9028 |
Brd 3 Dac 1 zero |
9029 |
Brd 3 Dac 1 span |
9030 |
Brd 3 Dac 2 zero |
9031 |
Brd 3 Dac 2 span |
9032 |
Brd 3 Dac 3 zero |
9033 |
Brd 3 Dac 3 span |
9034 |
Brd 3 Dac 4 zero |
9035 |
Brd 3 Dac 4 span |
9036 |
Brd 4 Dac 1 assignment |
9037 |
Brd 4 Dac 2 assignment |
9038 |
Brd 4 Dac 3 assignment |
9039 |
Brd 4 Dac 4 assignment |
9040 |
Brd 4 Dac 1 zero |
9041 |
Brd 4 Dac 1 span |
9042 |
Brd 4 Dac 2 zero |
9043 |
Brd 4 Dac 2 span |
9044 |
Brd 4 Dac 3 zero |
9045 |
Brd 4 Dac 3 span |
9046 |
Brd 4 Dac 4 zero |
9047 |
Brd 4 Dac 4 span |
9048 -9095 |
|
|
|
file 4 [0][] |
|
9100 - 9107 |
Bit map of states of each zone. |
|
Bits 0 to 8 why not sampling; 0 = OK, 1 = blocking sample. |
|
bit 0 = Zone activeX == 0, this clears all other bits. |
|
bit 1 = pump modeX == 0 |
|
bit 2 = Digital input blocking sample |
|
bit 3 = base statusX = 0 (may be ON delay) |
|
bit 4 = Min TC (note if set Min MV is not tested) |
|
bit 5 = Min MV |
|
bit 6 = calibration |
|
bit 7 = Auto cal |
|
bit 8 = sample controlX == 0 (probably caused by one of the previous) |
|
Bits 9 to 11 |
|
Bits 12 to 14 blocking COF/PF adjust |
|
bit 12 = IR modeX not 1 or 2 |
|
bit 13 = base status not 4 |
|
bit 14 = digital input blocking adjust. |
|
Bit 15 NU |
9100 - 9147 |
|
9148 |
Surface carbon activity |
9149 |
Carbon with alloy factor = 1 |
9150 |
Carbon with specified alloy factor |
9151 |
carbon calculated from only CO and CO2 with alloy factor = 1 |
9152 |
carbon calculated from only CO and CO2 with supplied alloy factor |
9153 |
IR %C based on original 3 gas calculation |
9154 |
Digital inputs from Dig I/O boards |
|
bits 0 to 3 from brd 1, 4 to 7 from brd 2, 8 to 11 from brd 3, and 12 to 15 from brd 4 |
|
bits 0 to 7 are PF/COF inhibit for zones 0 thru 7 |
|
bits 8 to 15 are stop sample for zones 0 thru 7 |
9155 |
Custom sequence pointer |
9156 - 9187 |
first of 32 points for custom sequence |
9188-9190 |
|
9191 |
Que_[0][][] status |
9192 |
Que_[1][][] status |
9193 |
Que_[2][][] status |
9194 |
Que_[3][][] status |
9195 |
Que_[4][][] status |
9196 |
Que_[5][][] status |
9197 |
generic que inst number |
9198 |
generic que register |
9199 |
generic que data |
|
|
file 4 [1][] |
|
8900 |
ambient temperature; deg F x 100 |
8901 |
gas (cell) temperature, deg F x 100 |
8902 |
cell abs pressure |
8903 |
cell differential pressure |
8904 |
gas 1 peak to peak |
8909 |
gas 1 level at zero (N2) |
8914 |
gas 1 gain constant from span |
8919 |
gas 1 reading with compensation |
8924 |
gas 1 value |
8929 |
gas 1 positive |
8934 |
gas 1 negative |
8939 |
gas 1 value with TC adjust |
8944 |
gas 1 value with press adjust |
8949 |
gas 1 value with both |
8954 |
temperature ratio Tcal/T |
8959 |
pressure ratio P/Pcal |
8964 |
filter time in MS |
8969 |
Integer of calibration average |
8974 |
Integer of gas read at ave |
8989 |
Ambient temperature pre-trim |
8990 |
Gas temperature pre-trim |
8991 |
Normalized Absorbance (CH4) |
8992 |
Normalized Absorbance (CO2) |
8993 |
Normalized Absorbance (CO) |
8994 |
Normalized Absorbance (CO2) |
8995 |
gas 1 p2p raw. |
|
|
file 5 |
|
8500 |
probe MV |
8508 |
probe COF |
8516 |
probe temperature |
8524 |
probe process factor |
8532 |
probe %C |
8540 |
probe carbon setpoint |
8548 |
IR temperature |
8556 |
H2 cell in % times 100 (xx.xx) |
8564-8567 |
|
8568 |
test mode CO data xx.xx |
8576 |
test mode CO2 data x.xxxx |
8584 |
test mode CO data xx.xx |
8592 |
test mode CO2 data xx.xx |
8600 |
PC_compare mode 0 = probe %C setpoint, 1 = probe %C actual |
8608 |
Compare IR %C to probe %C or Setpoint if 0 disable. |
8616 |
alarm bit map |
|
bit 0 = low flow; bit 1 = slave communications |
|
bit 2 = max factor; bit 3 = min factor; |
|
bit 4 = PC_comp alarm |
|
bit 5 = auto cal alarm |
|
bit 6 = NU |
|
bit 7 thru 15 = gas alarms (see Note below) |
8624 |
bit 0 = FC TC; Bit 1 = PB TC |
|
bit 2 = PB MV; bit 3 = PB COF/PF |
|
bit 4 = PB %C; bit 5 = ambient temperature |
|
bit 6 = gas temperature |
|
bit 7 thru 15 not assigned. |
8632 |
alarm 1 assignment bit mask 0 = not assigned; 1 = assigned |
8640 |
alarm 2 assignment bit mask 0 = not assigned; 1 = assigned |
|
bits 0 to 6 are alarm_bit_map1 bits (0 to 6) |
|
bits 7 to 15 are alarm_bit_map bits (7 to 15) |
|
alarm_bit_map bits 0 to 6 are always alarm 1 |
8648 |
Calculation flag 0 = COF, 1 = MMI PF |
8656 |
Status of base (0 = OFF, 1 = pump delay ON, 2 = sample delay, 3 = measure delay, 4 = delay OFF, 5 = ON.) |
8664 |
interval timer for COF/PF adjust |
8672 |
sample ON delay timer |
8680 |
sample OFF delay timer |
8688 |
CO2 high alarm limit |
8696 |
CO2 low alarm limit |
8704 |
CO high alarm limit |
8712 |
CO low alarm limit |
8720 |
CH4 high alarm limit |
8728 |
CH4 low alarm limit |
8736 |
CO2H high alarm limit |
8744 |
CO2H low alarm limit |
8752 |
IR %C high alarm limit |
8760 |
IR %C low alarm limit |
8768 |
H2 high alarm limit |
8776 |
H2 low alarm limit |
8784 |
O2 high alarm limit |
8792 |
O2 low alarm limit |
8800 |
furnace TC High alarm limit |
8808 |
furnace TC Low alarm limit |
8816 |
probe TC High alarm limit |
8824 |
probe TC Low alarm limit |
8832 |
probe MV High alarm limit |
8840 |
probe MV Low alarm limit |
8848 |
probe COF/PF High alarm limit |
8856 |
probe COF/PF Low alarm limit |
8864 |
probe %C High alarm limit |
8872 |
probe %C Low alarm limit |
8880 |
O2 data mantissa |
8888 |
O2 data exponent |
8896-8899 |
|
|
|
file 9 |
|
900 |
product ID code |
901 |
reset logging |
902 |
Dynamic C compiler version in hex |
903 |
long date/time stamp in secs from |
904 |
midnight Jan 1, 1980. |
905 |
Hack attempts counter |
906 |
Web access code, level 1 |
907 |
Web access code, level 2 |
908 |
SSI error handler return counts |
909 |
Set factory defaults control, 23205 (0x5aa5) to set |
910 |
Force user block write and read |
911 |
Rabbit ID from ID block |
912 |
Web CGI action |
|
|
914 |
4 locations for IP address (14 - 17) |
918 |
4 locations for netmask (18 - 21) |
922 |
4 locations for gateway (22 - 25) |
|
|
930 |
10 locations for port states |
940 |
auto calibration interval timer |
941 |
auto zero interval timer |
942 |
auto cal/zero request; bit 0 = zero, bit 1 = span |
943 |
auto cal/zero sequence |
944 |
sequence timer |
945 |
auto cal/zero status |
946 |
Flag to initiate log of Auto cal |
947 |
Number of entries in Auto cal log file |
|
|
980 |
4 locations for Time server IP address (120 - 123) |
984 |
UTC time zone as a quarter hour offset from UTC must be +/- 100 |
|
For EST with a -5 hour difference enter -20. |
985 |
UTC update interval in days (0 to 399) 0 disables |
986 |
UTC update flag |
987 |
UTC result |
988 - 989 |
|
990 |
DAC board number. 1 thru 8 |
991 |
|
992 |
|
993 |
|
994 |
|
995 |
|
996 |
|
997 |
|
998 - 999 |
|
|
|
2600 - 2699 |
Four Quad DAC boards |
2700 - 2799 |
Four Quad DAC boards |
0 - 14 |
|
0 |
DAC status = copy of COM_stat_X |
1 |
DAC mode, 0 = counts, 1 = current |
2 |
DAC 0 Value Current 0 to 20000 |
3 |
DAC 1 Value |
4 |
DAC 2 Value |
5 |
DAC 3 Value |
6 |
DAC calibration channel |
7 |
DAC calibration Enable |
8 |
DAC calibration request |
9 |
DAC calibration target value CH 1 |
10 |
DAC calibration target value CH 2 |
11 |
DAC calibration target value CH 3 |
12 |
DAC calibration target value CH 4 |
13 |
|
14 |
|
15 to 19 |
|
20 |
computed values to send to DAC |
21 |
|
22 |
|
23 |
|
24 |
|
|
|
2800 - 2899 |
|
0 |
Com status for message one of the PIC to rabbit comms. |
1 - 3 |
|
4 |
Com status for message two of the PIC to rabbit comms. |
5 - 15 |
|
16 |
A/D 1 status register (negative) |
17 |
A/D 1 reading, ir led on |
19 |
A/D 1 status register (positive) |
20 |
A/D 1 reading, ir led off |
22 |
A/D 2 status register (negative) |
23 |
A/D 2 reading, ir led on |
25 |
A/D 2 status register (positive) |
26 |
A/D 2 reading, ir led off |
28 |
A/D 3 status register (negative) |
29 |
A/D 3 reading, ir led on |
31 |
A/D 3 status register (positive) |
32 |
A/D 3 reading, ir led off |
34 |
A/D 4 status register (negative) |
35 |
A/D 4 reading, ir led on |
37 |
A/D 4 status register (positive) |
38 |
A/D 4 reading, ir led off |
40 |
IR LED trigger time |
41 |
time from IRLED on/off to trigger AD7739 conv. |
42 |
internal A/D channel selector |
43 |
ambient temperature raw counts (10 bits resolution) |
44 |
ambient temperature trim |
45 |
gas temperature raw counts (10 bits resolution) |
46 |
gas temperature trim |
47 |
absolute pressure raw counts (10 bits resolution) |
48 |
absolute pressure trim |
49 |
differential pressure raw counts (10 bits resolution) |
50 |
differential pressure trim |
51 |
digital status word |
52 |
Baud Rate selection variable |
53 - 99 |
|
|
|
2900 - 2999 |
|
2900-2903 |
|
2904 |
Digital Output setpoint |
2905 |
Digital Output actual |
2906 |
Digital Input |
2907-2913 |
|
2914 |
Digital Output setpoint |
2915 |
Digital Output actual |
2916 |
Digital Input |
2917-2923 |
|
2924 |
Digital Output setpoint |
2925 |
Digital Output actual |
2926 |
// Digital Input |
2927-2933 |
|
2934 |
Digital Output setpoint |
2935 |
Digital Output actual |
2936 |
Digital Input |
2937-2949 |
|
2950 |
x curve point in MV |
2951 |
y curve point in 10x MV (10000 = 1000.0) |
2952-2999 |
more curve points. |
2998 |
top curve point is forced to 3200 for x |
2999 |
top curve point is forced to 32000 for y |
|
|
3000 - 3099 |
|
3100 - 3199 |
|
3200 - 3299 |
|
3300 - 3399 |
|
1 |
version number of the firmware |
2 |
0 = °F, 1 = °C, 2 = °R, 3 = K |
3 |
Cold Junction Temperature |
8 |
Input type |
13 |
Process Variable |
18 |
enables a calibration |
19 |
CJ cal or zero/span voltage cal |
20 |
Calibration Range register. Sets the voltage gain for a calibration |
21 |
|
22 |
First of 5 Calibration value |
27 |
First of 5 calibration timers |
32 |
0 = no calibration, 1 = calibration in progress |
33 |
First of 5 calibration error calculations |
37 |
End of calibration registers |
38 |
First of 5 Scaled VDC |
|
|
|
|
3400 - 3499 |
|
0 - 10 |
|
11 |
|
12 - 77 |
|
78 |
|
78 - 99 |
|
|
|
3700 - 3799 |
|
0 - 9 |
|
10 -17 |
8 registers for zone probe MV |
18 - 25 |
8 registers for zone probe TC |
26 - 33 |
8 registers for zone furnace TC |
34 - 99 |
|
Note:
Gas Numbers |
Gas alarm bits (for register 8616): |
0 = CO |
7 = CO2 |
1 = CO2 |
8 = CO |
2 = CH4 |
9 = CH4 |
3 = High CO2 |
10 = High CO2 |
4 = IR %C |
11 = IR %C |
5 = H2 |
12 = H2 |
6 = O2 |
13 = O2 |
7 = Probe %C |
|
|