- Phone:513.772.0060
- Address:7205 Edington Dr. Cincinnati, OH 45249
The Series 8 is SSi’s affordable line of process and high limit controllers. These products are used for many thermal processing and indicating applications. The Series 8 has universal inputs with relays and analog outputs allowing for versatility and a wide range of monitoring or controlling applications. With 3 options for sizes (1/16, 1/8 and ¼ DIN), the panel mount unit offers high accuracy universal inputs for PID control and high limit protection.


| Built-In Timers (808, 808SR, 816, 804 Models) |
| Configurable Alarms: High, Low, Deviation, Band, Timer Complete |
| Auto-Tuning, Smart Tuning |
| Modbus 485 Comms |
| 3 Configurable Relay Outputs |
| 4-20mA Output (Models 804, 808) |
| 24 V transmitter/supply (Models 804, 808) |
| 3 sizes: 1/4 DIN, 1/8 DIN, 1/16 DIN |
| FM Approved, UL Listed, and CE Marked |
| Designed to combine temperature and timer operation for a temper/draw furnace |
| Easy-to-use logic inputs for push button operation of timer |
| Automatically download set point and time from SCADA software |
| Calibration Accuracy: <±0.25% of reading ±1LSD |
| Thermocouple Types: K, J, N, R, S, B, L, T, C Custom, RTD, and linear V and mA |
| Series 8 Configuration Software |
| Model Name | Model Number | Size | Relay | FM Relay | 4-20mA Output | SSR Drive Output | Digital Inputs | Slidewire | RS485 Modbus RTU | Timer | FM Approval |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 808 | 31343 | 1/8 DIN | 3 | 1 | 2 | X | X | ||||
| 808R | 31345 | 1/8 DIN | 3 | 1 | 2 | X | X | ||||
| 808L | 31346 | 1/8 DIN | 3 | 1 | 2 | X | X | ||||
| 816 | 31347 | 1/16 DIN | 3 | 1 | X | X | |||||
| 816L | 31348 | 1/16 DIN | 2 | 1 | 1 | X | X | ||||
| 804 | 31349 | 1/4 DIN | 3 | 1 | 2 | X | X | X | |||
| 804L | 31350 | 1/4 DIN | 3 | 1 | 2 | X | X |
| Relay Output (Form A, N.O.) |
|---|
| Isolated output 300 Vac CAT II |
| Contact rating: 2A, 230 Vac ±15% resistive |
| Logic (SSR Drive) Output (808R only) |
|---|
| Not Isolated |
| Output ON slate: 12Vdc @ 40mA max |
| Output OFF slate: <300mV, <100µA |
| Output switching rate must be set to prevent damage to output device |
| Relay Output (Form A, N.O.) |
|---|
| Isolated output 300 Vac CAT II |
| Contact rating: 2A, 230Vac ±15% resistive |
| Relay Output (Form A, N.O.) Models 808R, 808L, and 804L only |
|---|
| Isolated output 300 Vac CAT II |
| Contact Rating: 2A, 230Vac ±15% resistive |
| Changeover Relay (Form C) |
|---|
| Isolated output 300 Vac CAT II |
| Contact rating: 2A, 230Vac ±15% resistive. |
| NOTE: In FM versions, this output is FM approved and activated by Alarm 2 |